Our range of products include pilz pnoz x1 safety relays.
₹ 10600 / Piece Get Latest Price
| Number Of Poles | 2 Pole |
| Brand | Pilz |
| Usage/Application | Industrial |
| Model Name/Number | PNOZ X1 |
| Color | Yellow |
| Frequency | 50HZ |
| Surface Finishing | Polished |
| Supply Voltage AC/DC | 24V |
| Power Consumption At AC | 4.0 VA |
| Power Consumption At DC | 2.0 W |
| Amplitude | 0.35 mm |
| Dimension : (LxWxH) | 87 x 25.5 x 121 mm |
| Weight | 180g |
| Residual ripple DC | 160% |
| Auxiliary Contacts: | 10A |
| Safety Contacts: | 6A |
Unit description
The safety relay meets the requirements of EN 60204-1 and IEC 60204- 1 and may be used in applications with
E-STOP pushbuttons
The safety relay is not suitable for noncontact barriers because
A dynamic start is not possible
The unit can be started during the delay-on de-energisation time
Function description
Single-channel operation: No redundancy in the input circuit, earth faults in the reset circuit are detected.
Automatic start: Unit is active once the input circuit has been closed.
Manual reset: Unit is active once the input circuit is closed and then the reset circuit is closed.
Increase in the number of available contacts by connecting contact expander modules or external contactors/relays.
Wiring Please note: Information given in the “Technical details” must be followed.
Outputs 13-14, 23-24, 33-34 are safety contacts, output 41-42 is an auxiliary contact (e.g. for display).
To prevent contact welding, a fuse should be connected before the output contacts (see technical details).
Calculation of the max. cable runs l max in the input circuit: Rlmax = max. overall cable resistance (see technical details) Rl /km = cable resistance/km
Use copper wire that can withstand 60/75 °C. ` Sufficient fuse protection must be provided on all output contacts with capacitive and inductive loads.
Key
Power: Supply voltage
Reset/start: Reset circuit Y1-Y2
Input: Input circuits A1-L+
Output safe: Safety contacts 13-14, 23-24, 33-34
Output aux: Auxiliary contacts 41- 42
A: Automatic reset ` d: Manual reset
B: Input circuit closes before reset circuit
C: Reset circuit closes before input circuit
T1: Switch-on delay
T2: Delay-on de-energisation
Installation
The safety relay should be installed in a control cabinet with a protection type of at least IP54.
Use the notch on the rear of the unit to attach it to a DIN rail.
Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing element (e.g. retaining bracket or an end angle).